====== Cooling maintenance ====== ===== Cooled doors ===== ==== Per year ==== ­Check if flux is cold after doors. ­Use thermal camera to check doors temperature. ===== Encountered problems and solutions ===== ==== Cooled doors ==== ­-> Out air flux is not cold. * Use thermal camera to ensure and compare with other doors. * Inspect water arrival and departure pressure if possible. * Check water quality and PH. * Determine cooled door heat exchanger material and inspect if galvanic corrosion is not occurring. * If blocked, dismount door and purge it. Have a special look on solid particles removed: color and aspect are important indicators to identify problem and prevent future fill. ­-> Condensation occur on heat exchanger surface * Check water temperature and air temperature/humidity, report them in humid air chart and check, dew point is probably reached. ==== Humidifier ==== ­-> Humidifier is continuously running, or often running (causing electricity, water and maintenance costs) * Check room humidity with a different probe than the one dedicated. * Check room humidity regulation. * Check room air position on humid air chart, and check it doesn’t reach condensation point. * Check room sealing. ­-> Humidifier is always/often asking for maintenance * See Humidifier is continuously running, or often running. * Check inlet water quality. * Have the equipment checked by a professional. ==== Air handling unit ==== ­-> Condensation occur on heat exchanger surface * Check water temperature and air temperature/humidity, report them in humid air chart and check, dew point is probably reached. ­-> Compressor is used even with cold water supply * Check water valves are opened. * Check if probes values are coherent. * Check regulation * If air temperature regulation is too low, unit may use compressor to respond to this high cooling demand. * If humidity in room is too high, unit will condensate only and not lower temperature (i.e. high load). * Check internal pipes are not blocked by a fill.